APC (American Power Conversion) Smart-UPS (Rev 1.8.1)
Specification
Input
Nominal input voltage: single phase 220 / 230 / 240 Vac.
Nominal input frequency: 50 or 60 Hz, internally selected by microprocessor.
Input Protection: 12 Amp resettable circuit breaker.
Transfer characteristics
Frequency limits for on-line operation: 50 or 60 Hz, ± 5%.
Lower input voltage limit for 173 Vac; when set for operation at the on-line operation:
nominal
240 Vac line, the lower input voltage limit is increased to 180 Vac.
Upper input voltage limit for 253 Vac; when set for operation at the 240 on-line
operation: Vac line, the upper input voltage limit is increased to 264 Vac.
SmartBoost operation input voltage range: 173 to 196 Vac; when set for operation at the
nominal 240 Vac line, SmartBoost input voltage range is increased to 180 to 204 Vac.
Transfer time: 2 ms typical, 4 ms maximum.
Output characteristics
Maximum load: 900 VA or 630 W @ 0.70 power factor.
On-battery output voltage: 225 Vac ± 5%.
On-battery frequency: 50 or 60 Hz, ± 0.1 Hz unless synchronised to mains frequency during
utility brownout.
On-battery waveshape: low distortion sinewave.
Protection: overcurrent and short circuit protected, latching shutdown upon overload.
Noise and surge suppression
Surge energy rating : 480 J (one time, 10/1000 µs waveform).
Surge current capability: 6500 Amp peak maximum (one time, 8/20 µs waveform).
Surge response time: 0 ns (instantaneous) normal mode, < 5 ns common mode.
Surge voltage let-through: < 2% of applied ANSI C62.41 Category A ± 6 kV test
waveform.
Noise filter: normal and common mode EMI / RFI suppression, 100 kHz to 10 MHz.
Battery and charger
Battery type: spill proof, maintenance free sealed lead-calcium.
Typical battery life: 3 to 6 years - depends on number of discharge cycles and ambient
temperature.
Typical recharge time: 4 to 10 hours from total discharge. UPS may be used immediately
after discharge but will provide shorter run time.
Environment
Operating temperature: 0°C to 40°C (32°F to 104°F).
Storage temperature: -15°C to 45°C (5°F to 113°F).
Operating and storage relative humidity: 0 to 95%, non-condensing.
Operating elevation: 0 to 3,000 m (10,000 ft).
Storage elevation: 0 to 15,000 m (50,000 ft).
Electromagnetic immunity: IEC 801-2, 801-3, 801-4, 801-5; severity levels III or IV.
Audible noise: < 45 dBA at 1 m (3 ft).
Physical
Size: 23.1 cm H x 17.5 cm W x 45.2 cm D (9.1" x 6.9" x 17.8").
Weight: 19.5 kg (43lbs), shipping weight is 21.8 kg (48 lbs).
Approvals
Safety approvals: UL per 1778, CSA per C22.2, TUV per IEC 950.
EMC verification: FCC, DOC Class A and B verified; VCCI Class 2 compliance; EN55022 Class
B verified.
 
|